Basic parameters |
Primary Current(A) |
Secondary Current(mA) |
Burden |
Max Current(A) |
Accuracy Class |
Note |
Rb(Ω) |
30 |
12 |
10 |
120 |
0.2~0.1 |
DC 38.2A |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Current error and phase error limits |
Accuracy Class |
Current error ±(%) |
phase error(′) |
In the following currents |
In the following currents |
0.01In |
≥0.05In |
0.01In |
0.05In |
0.2In |
1In |
2In |
3In |
Imax |
0.1 Class |
0.2 |
0.1 |
15 |
8 |
5 |
5 |
5 |
5 |
5 |
0.2 Class |
0.4 |
0.2 |
30 |
15 |
10 |
10 |
10 |
10 |
10 |
Note: When current is 0.2In~Imax, phase error(δe ) is the average of δmax and |
δmin; When current is i, the phase error of i is the difference of betweenδi and δe. (△δi=δi-δe). |
|
When Current is 84.8A, the electric energy measurement error introduced by current transformers is less than 3% |
Sine-half wave test |
Normal Service Conditions |
Ambient temp.(℃):-40℃~+70℃; Relative Humidity :≤98(25℃); Altitude :≤3000m |
The main electrical performance |
And a winding secondary winding voltage between the tolerance of not less than 4 kV, insulation resistance of not less than 1000MΩ |
Reference size(mm) |
A |
B |
C |
D |
E |
|
|
|
|
|
|
|
|
|
35 |
17 |
17 |
φ7.5 |
20 |
|
|
|
|
|
|
|
|
|